CT Saturation & Burden Calculator
Enter the CT ratio, excitation-curve points, secondary circuit burden, fault current, X/R ratio, and remanence. The calculator estimates first-cycle composite error, time to a 10% peak-current error, and the primary fault current that reaches that reference.
First-cycle accuracy statusBelow 10% reference (0.00% composite error)
- First-cycle composite error
- 0%
- Time to 10% peak-current error
- Not reached
- Actual first-cycle secondary current (A RMS)
- 74.47
- Peak actual secondary current (A)
- 125.28
- Peak excitation voltage (V)
- 72.91
- Total resistive burden (ohm)
- 0.58
- Rated-current burden (VA)
- 7.05
- Maximum primary fault current at 10% error
- 34,523.8
Ideal vs actual secondary-current waveform
| Time (ms) | Ideal A | Actual A | Excitation A | Marker |
|---|---|---|---|---|
| 0 | 0 | 0 | 0 | |
| 2.5 | -23.81 | -23.81 | -0 | |
| 5 | -82.28 | -82.28 | -0 | |
| 7.5 | -123.12 | -123.12 | -0 | |
| 10 | -108.85 | -108.85 | -0 | |
| 12.5 | -47.75 | -47.75 | -0 | |
| 15 | 13.07 | 13.07 | -0 | |
| 17.5 | 26.44 | 26.44 | -0 | |
| 20 | -15.87 | -15.87 | -0 | |
| 22.5 | -76.44 | -76.44 | -0 | |
| 25 | -102.95 | -102.95 | -0 | |
| 27.5 | -71.37 | -71.37 | -0 | |
| 30 | -5.7 | -5.7 | -0 | |
| 32.5 | 41.78 | 41.78 | -0 | |
| 35 | 33.66 | 33.66 | -0 | |
| 37.5 | -21.77 | -21.77 | -0 | |
| 40 | -77.33 | -77.33 | -0 | |
| 42.5 | -85.85 | -85.85 | -0 | |
| 45 | -39.05 | -39.02 | -0.03 | |
| 47.5 | 25.66 | 25.7 | -0.04 | |
| 50 | 56.01 | 56.02 | -0.01 | |
| 52.5 | 27.97 | 27.98 | -0 | |
| 55 | -34.41 | -34.41 | -0 | |
| 57.5 | -78.86 | -78.85 | -0.01 | |
| 60 | -67.94 | -67.8 | -0.14 | |
| 62.5 | -9.93 | -9.52 | -0.41 | |
| 65 | 48.03 | 48.26 | -0.23 | |
| 67.5 | 58.77 | 58.81 | -0.05 | |
| 70 | 14.01 | 14.02 | -0.01 | |
| 72.5 | -48.81 | -48.79 | -0.02 | |
| 75 | -77.41 | -77.25 | -0.16 | |
| 77.5 | -47.76 | -46.84 | -0.92 | |
| 80 | 16.12 | 17.46 | -1.34 | |
| 82.5 | 61.95 | 62.4 | -0.45 | |
| 85 | 52.31 | 52.4 | -0.09 | |
| 87.5 | -4.53 | -4.48 | -0.04 | |
| 90 | -61.39 | -61.28 | -0.11 | |
| 92.5 | -71.12 | -70.42 | -0.7 | |
| 95 | -25.43 | -23.03 | -2.4 | |
| 97.5 | 38.26 | 40.16 | -1.9 | |
| 100 | 67.65 | 68.1 | -0.45 |
Uses the IEEE PSRC nonlinear excitation model with a fixed-step fourth-order Runge-Kutta solution.
The 10% comparison is an engineering reference, not a universal relay acceptance rule.
How to use this calculator
- Enter the CT ratio and two manufacturer excitation-curve points from the saturated straight-line region.
- Enter winding resistance, one-way lead length, lead resistance, connected-device burden, and burden power factor.
- Enter the symmetrical fault current, X/R ratio, initial DC offset, remanence, frequency, and simulation duration.
- Read the composite error, burden values, reverse 10% fault-current result, and waveform table.
How the CT saturation result is calculated
The calculator follows the nonlinear excitation model used in the IEEE PSRC CT saturation calculator theory. It treats the CT secondary as an ideal current source feeding winding resistance, lead resistance, relay burden, and a nonlinear exciting branch. The two excitation-curve points define the saturated log-log slope rather than a simple knee-point pass/fail check.
First it calculates the ratio N = IPR / ISR, where IPR is rated primary current and ISR is rated secondary current. From excitation points (Ie1, Ve1) and (Ie2, Ve2), it calculates:
S = ln(Ie2 / Ie1) / ln(Ve2 / Ve1)
Vs = Ve1 x (10 / Ie1)^(1 / S)
S is the inverse log-log saturation exponent, and Vs is the extrapolated RMS excitation voltage at 10 A exciting current. The relay VA is converted to impedance at rated secondary current. Round-trip lead resistance is 2 x length x resistance / 1000. The total resistive burden is winding resistance plus lead resistance plus the resistive part of device burden.
The ideal secondary current includes AC fault current and a decaying DC offset:
is(t) = (sqrt(2) Ip / N) x [cos(wt - phi0) - Off x exp(-t / tau)]
The CT flux linkage is then integrated with a fixed-step fourth-order Runge-Kutta method. At each step, exciting current is calculated from flux linkage as ie = A x sign(lambda) x abs(lambda)^S, actual secondary current is i2 = is - ie, and excitation voltage is d lambda / dt.
What the reported error means
First-cycle composite error is the RMS error current over the first complete cycle divided by the RMS ideal secondary current for that same cycle:
error = 100 x sqrt(integral(ie^2 dt) / integral(is^2 dt))
The 10% result is a visible engineering reference. It is not a universal acceptance rule for every relay element. Some schemes tolerate more transient error, while differential, high-impedance, distance, and sensitive overcurrent applications may need a more detailed relay-specific review.
What moves the answer most
Higher fault current, higher X/R ratio, reinforcing remanence, longer leads, higher winding resistance, and larger connected burden all push the CT toward saturation. A 1 A secondary usually handles long leads better than a 5 A secondary because the same VA burden corresponds to a larger impedance but much lower current through the leads.
What this calculator leaves out
This is a screening model. It simplifies below-knee excitation behavior and does not model hysteresis loops, eddy-current loss, leakage reactance, residual flux history, frequency-dependent material behavior, relay algorithm response, or current-limiter and breaker timing. Use actual excitation and winding-resistance data when possible, and confirm final protection decisions with relay-manufacturer guidance and a qualified protection engineer.
Worked example
For a 1200:5 CT with excitation points of 1 A at 360 V and 10 A at 400 V, the saturated-curve exponent is ln(10 / 1) / ln(400 / 360) = 21.85, and the extrapolated 10 A voltage is 400 V RMS. With 100 ft one-way No. 10 copper example leads at 1.21 ohm/1000 ft, lead resistance is 2 x 100 x 1.21 / 1000 = 0.242 ohm.
Add 0.3 ohm CT winding resistance and a 1 VA unity-power-factor device burden on a 5 A secondary, which is 1 / 5^2 = 0.04 ohm. The total resistive burden is 0.582 ohm, and the external rated-current burden is 7.05 VA. With a 12 kA symmetrical primary fault, X/R of 12, 100% DC offset, no remanence, and a 60 Hz system, the first-cycle composite error is effectively 0.00%, the actual first-cycle secondary current is about 74.47 A RMS, peak excitation voltage is about 72.91 V, and the reverse solver finds about 34,524 A primary for a 10% first-cycle composite-error reference.
Common questions
What causes a protection CT to saturate during a fault?
A fault drives secondary current through the CT winding, leads, relays, and meters. The voltage needed to push that current through the burden increases flux in the core. High burden, high fault current, DC offset, and remanence can push the core into the saturated part of its excitation curve.
How do I choose two excitation-curve points?
Use two points from the approximately straight saturated portion of the manufacturer log-log excitation curve. Do not use points from the flat below-knee region or two nearly identical voltages, because they do not describe the saturated slope well.
Is 10% composite error always the acceptance limit?
No. The 10% value is a common reference for comparing CT performance, but relay behavior depends on the protection element, settings, fault type, and operating time. Treat this result as a screening flag, not as a universal pass or fail rule.
Why does lead resistance matter so much for 5 A CTs?
Lead voltage drop rises with current, so 5 A secondaries can spend much more of the CT voltage capability in the cable. A 1 A CT often tolerates long leads better because the lead current is lower for the same primary current ratio style.
What does remanence do to time to saturation?
Remanence starts the core with residual flux already present. If its polarity reinforces the fault-produced flux, saturation can occur sooner; if it opposes that flux, saturation can be delayed until the transient flux changes direction.
Can this evaluate a differential or high-impedance scheme?
It can show CT secondary-current distortion for the entered CT and burden, but it does not model relay operating characteristics, spill current, stabilizing resistors, varistors, or through-fault security rules. Use it as one input to a scheme-specific protection study.